+(91)-9871034100
PHONE NO
07AOSPS8386M1ZM
GST NO

admin

Differential Pressure Transmitters DPT30-R8 Series

Sensocon USA Series DPT30-R8 Range Differential Pressure Transmitter

 
Response Time0.8 – 4.0, jumper selectable
Maximum Pressure100 in w.c.
Power Supply24 VDC or VAC, +/- 10%
Enclosure RatingIP 54/ NEMA 3
Display3 1/2 Digit LCD Backlit LCD
Media CompatibilityDry air or non-aggressive gases

The Series DPT Multi-Range Differential Pressure Transmitter was designed specifically for the building automation and HVAC industry. With field selectable ranges down to 0.1 inches w.c., this product is ideal for monitoring building pressure, static pressure, differential pressure, or air velocity and flow. The Series DPT Differential Pressure Transmitter also has jumper selectable outputs for 4-20 mA or 0-10 V and unit selection giving additional flexibility. For a virtually maintenance free transmitter, order the optional automatic zero and the transmitter will perform its own zero point maintenance. The Multi-Range Differential Pressure Transmitter also has an optional backlit LCD for giving local indication.

Specification:

  • Maximum Pressure:100 in w.c.Media compatibility:Dry air or non-aggressive gases Accuracy:Ranges < 0.5 in w.c. = +/- 0.01 in w.c.Ranges ≥ 0.5 in w.c. = +/- 1.5%includes thermal effects, linearity, hysteresis,repeatability, and long term stability.Temperature Ranges:Compensated: 14° to 122°F Operating: 14° to 122°F
  • Response Time:0.8 – 4.0, jumper selectable Power Supply:24 VDC or VAC, +/- 10%Output:Voltage: 3-wire 0 – 10V or 0 – 5V, jumper selectable Power Consumption: <1.0WMinimum Resistance: 1kΩCurrent: 3-wire4 – 20mAPower Consumption: <1.2WMaximum Load: 500ΩEnclosure Rating:IP 54/ NEMA 3Display:3 ½” Digit LCD Backlit LCD
  • Electrical Connections:Screw terminal block

Model Number:
DPT30-R8         
inWC  -5.0 – 5.0 -10.0 – 10.0-15.0 – 15.0 0 – 10 0 – 15 0 – 20 0 – 25 0 – 30 
 Pa -1250 – 1250 -2500 – 2500 -3750 – 3750  0 – 2500 00 – 3750 0 – 5000 0 – 6250 0 – 7500 
mbar  -12.5 – 12.5 -25 – 25 -37.5 – 37.5 0 – 25 0 – 37.5  0 – 500 – 62.5  0 – 75 
mmWC -127 – 127 -254 – 254 -380 – 380   0 – 2540 – 3800 – 508 0 – 635 0 – 762 
 

Differential Pressure Transmitter DPT10-R8 SERIES

Sensocon USA Series DPT10-R8 Range Differential Pressure Transmitter

 
BrandSensocon
Response Time0.8 – 4.0, jumper selectable
Maximum Pressure100 in w.c.
Power Supply24 VDC or VAC, +/- 10%
Display3 1/2 Digit LCD Backlit LCD
Enclosure RatingIP 54/ NEMA 3
Minimum Resistance1kOhm


The Series DPT Multi-Range Differential Pressure Transmitter was designed specifically for the building automation and HVAC industry. With field selectable ranges down to 0.1 inches w.c., this product is ideal for monitoring building pressure, static pressure, differential pressure, or air velocity and flow. The Series DPT Differential Pressure Transmitter also has jumper selectable outputs for 4-20 mA or 0-10 V and unit selection giving additional flexibility. For a virtually maintenance free transmitter, order the optional automatic zero and the transmitter will perform its own zero point maintenance. The Multi-Range Differential Pressure Transmitter also has an optional backlit LCD for giving local indication.

Specification:

  • Maximum Pressure:100 in w.c.Media compatibility:Dry air or non-aggressive gasesAccuracy:Ranges < 0.5 in w.c. = +/- 0.01 in w.c.Ranges ≥ 0.5 in w.c. = +/- 1.5%includes thermal effects, linearity, hysteresis,repeatability, and long term stability.Temperature Ranges:Compensated: 14° to 122°FOperating: 14° to 122°F
  • Response Time:0.8 – 4.0, jumper selectablePower Supply:24 VDC or VAC, +/- 10%Output:Voltage: 3-wire 0 – 10V or 0 – 5V, jumper selectablePower Consumption: <1.0WMinimum Resistance: 1kΩCurrent: 3-wire4 – 20mAPower Consumption: <1.2WMaximum Load: 500ΩEnclosure Rating:IP 54/ NEMA 3Display:3 ½” Digit LCD Backlit LCD
  • Electrical Connections:Screw terminal block


Model Number:

DPT10-R8         
 inWC-0.5 – 0.5 -2.5 – 2.5 -5.0 – 5.0 0 – 0.5  0 – 1.00 – 2.5 0 – 5.0  0 – 10.0
Pa -125 – 125 -622 – 622 -1250 – 1250  0 – 125 0 – 2500 – 622 0 – 1250 0 – 2500 
mbar  -1.25 – 1.25 -6.2 – 6.2 – -12.5 – 12.5 0 – 1.25 0 – 2.5 0 – 6.2 0 – 12.5 0 – 25 
 mmWC-12.7 – 12.7 -64 – 64 -127 – 127 0 – 12.7 0 – 25.4  0 – 64 0 – 127  0 – 254

Aerosense Carbon Monoxide Transmitter Wholesaler

Ecmt200 Aerosense Caron Monoxide Transmitter

 
Minimum Order Quantity1 Piece
Accuracy+-2% of reading at the time of calibration
Model NumberECMT200
Display TypeDigital
Weight0.28 lb 0.11 kg
Response Time<45 seconds
BrandAerosense
Coverage Area5000 to 7000 sq. ft. typical
Temperature Limits-4 to 122 deg F (-20 to 50 deg C)
Storage Temperature32 to 68 deg F (0 to 20 deg C)
Humidity Limits15 to 90% RH
Current Output18 to 28 VDC
Voltage Output18 to 28 VDC/VAC

ECMT200 Aerosense Caron Monoxide Transmitter Series ECMT200, Carbon Monoxide Transmitter provides a field selectable current or voltage output that is proportional to the gas concentration in underground parking garages, vehicle maintenance facilities or mechanical rooms. Measurement range is upto 200 ppm. A field replaceable electrochemical sensor provides accurate readings upto 4 years.

Product Applications:
  • Garage Ventilation
  • Mechanical room monitoring
 

CMT-100 Aerosense Carbon Monoxide Transmitter

 
Minimum Order Quantity1 Number
ModelCMT-100
Usage/ApplicationGarage Ventilation
Response TimeWithin 5 minutes
Warm Up2 hours
Current Output4-20 mA
Voltage Output2-10 VDC
Power Input24VAC
Coverage Area4000 to 6000 sq. ft. typical
Measurement Range0-250 PPM
Storage Humidity0-95% RH (Non-Condensing)
Storage Temperature-30 to 60 deg C
Operating Humidity10-95% RH (Non-Condensing)
Operating Temperature-10 to 50 deg C

CMT-100 Aerosense Carbon Monoxide Transmitter Series CMT-100, Carbon Monoxide Transmitter designed to detect Carbon Monoxide gas in air with analog and RS-485 MODBUS output. Measurement range is upto 250 ppm and optional 300 ppm is available. It is 3-wired supporting and gives current, voltage and RS-485 MODBUS output.

Product Applications:
  • Garage Ventilation
  • Vehicle maintenance facility.
  • Pre-Calibrated
  • Convenient use with varying voltage application.
  • Easily installed at a low cost when used with exclusive case Semiconductor use to measure CO levels.
  • Provides output signal proportional to CO level Model available to interact with other Devices Optimum for parking lot, tunnel & under Ground places
 

Bourdon Type Pressure Gauge

H Guru Bourdon Pressure Gauge

 
Minimum Order Quantity12 Number
Dial Size2.5 inch / 63 mm
BrandH Guru
Pressure Range0 to 4 bar(0 to 60 psi)
UseHVAC Systems
Display TypeAnalog
Pressure TypeGauge Pressure
Connection TypeBSP
Connection Size1/4 inch
Dial TypeDry
Liquid FillingGlycerine
MountingBottom
Material of casingStainless Steel
Model Name/NumberH Guru Bourdon Pressure Gauge
Wetted PartsStainless Steel
Country of OriginMade in India

H Guru Bourdon Type Pressure Gauge

MODEL -PB

MACK – H. GURU INDIA

SIZE – 2.5′,4′,6′

ACC. – 2%

CONN. – BCPM

MNTG- 1/4′, 3/8′ BSP

RANGE – 4.2/60

Bourdon Type Pressure Gauge

 
Minimum Order Quantity12 Number
Dial Size2.5 inch / 63 mm
BrandH Guru
Pressure Range0 to 4 bar(0 to 60 psi)
UseHVAC Systems
Display TypeAnalog
Pressure TypeGauge Pressure
Connection TypeBSP
Connection Size1/4 inch
Dial TypeDry
Liquid FillingGlycerine
MountingBottom
Material of casingStainless Steel
Model Name/NumberBourdon Type Pressure Gauge
Country of OriginMade in India

Bourdon Type Pressure Gauge

  • MODEL -PB
  • MACK – H. GURU INDIA
  • SIZE – 2.5′,4”,6”
  • ACC. – 2%
  • CONN. – BCPM
  • MNTG- 1/4′, 3/8” BSP
  • RANGE – 4.2/60
 

Humidity and Temperature Sensors

The Inexpensive Transmitter

 
Voltage0…1/5/10 VDC
Response Time4 s
Supply Voltage12…28 VAC / 15…40 VDC
HousingABS
IPIP65
Current4-20 mA
Output NumberTwo freely scalable analog outputs


Backed with immense experience and understanding, we are recognized as one of the most prominent importers and exporters of Transmitter that offers stable and reliable Humidity and Temperature measurement. Be it in international or domestic market, our given Transmitters are cherished and acknowledged over the global platform. The entire array of Transmitter is checked upon a series of norms so as to assure its quality. Besides, we offer the Transmitter in a huge array of stipulations as per the requirements of our patrons.

 

Technical Information :

The HygroFlex1 series is the latest development in inexpensive HVAC transmitters for relative Humidity and Temperature. The devices are equipped with the tried-and-tested Hygromer® IN-1 sensor and boast unbeatable value for money. The optional ROTRONIC SW21 Software enables you to scale, calibrate and adjust (only Humidity) the Transmitter.

Technical Specification :

General

Transmitter type

2-wire type: HF120
3/4 wire type: HF13x

Supply voltage

12…28 VAC / 15…40 VDC

Current consumption

2-wire type max. 40mA
3/4 wire type
with voltage output: < 15 mA
with current output: < 55 mA

Parameters

Humidity and/or temperature

Housing material / IP

ABS / IP65

Weight

Wall version type W and A: 140 g
Duct version 100 mm type B and D: 140 g
Duct version 300 mm type E and F: 200 g
Space version type L and S: 90 g

Integrated sensors

Yes

Operating and measurement range

-20…50oC / 0…100 %RH (non-condensing)

CE / EMC compatibility

2004/108/EC

Humidity Measurement

Humidity sensor

ROTRONIC Hygromer® IN-1

Accuracy at 23 oC +5 K

<3 %RH (10…90 %RH)

Long-term stability

<1.5 %RH per year

Response time τ63

30 s (63 % of a jump 35…80 %RH) without ???lter

Temperature Measurement

Sensor

Thermistor

Standard temperature scale

0…50oC or 0…100oF

Accuracy at 23oC +5 K

+ 0.3oK (0…50oC)

Response time

4s

Outputs

 

Number

Two freely scalable analog outputs

Current

4…20 mA

Voltage

0…1/5/10 VDC

Air Velocity and Temperature Transmitter EE75 Series

 
Output Value0 – 10 V or 4 – 20 mA (Adjustable by jumpers)
Accuracy+/- 0.2m/s 3% mv
Model NumberEE75 Series
TypeTransmitter
Measuring RangeUp to 40 m/s
Working Temperature40 to 120 deg C

Our Air Velocity Transmitters EE75 Series has a huge demand in the market due to its sturdy construction and high efficiency. These products are widely appreciated among our clients and we provide them in different specifications as per the requirement. Our Air Velocity EE75 Series is extensively used in numerous industries for diverse applications. We also offer them in various customizations to meet the different customer demands. The EE75 Series Air Velocity Transmitters were developed to obtain accurate measuring results over a wide range of Velocities and Temperatures. A high-quality hot film sensor element based on cutting- edge thin film technology ensures maximum sensitivity, even at lowest mass flows. At the same time, the innovative probe design produces reliable measuring results at high flow velocities of up to 40m/s (8000fVmin). The integrated Temperature compensation minimizes the Temperature cross-sensitivity of the EE75 Series which, combined with the robust mechanical design, allows it to be used at process Temperatures between -40 to 120°C(-40 to 248°F).

Other Details:

  • In addition to Air Velocity and Temperature values, the Transmitter calculates the volumetric flow rate in m3/h or ft3/min. The cross section of the duct needs to be determined for this purpose and the volumetric flow rate can be displayed and directed to one of the analogue outputs. The EE75 Series can be used to measure the velocity of other gases as well, although a correction has to be applied to the unit at the factory.
 

Aerosense Clean Room Monitor Distributor Channel Partners

Aerosense Series ADPRHT Clean Room Monitor

 
Minimum Order Quantity1 Number
BrandAerosense
Usage/ApplicationPharma Cleanrooms,Hvac,Environmental,Pharma Machinery,Across Filters,Hospital Isolation Room
MaterialABS
Model Name/NumberAerosense Series ADPRHT
SizeEnclosure 74(W) x 72(H) x 40(D) mm
Electrical Supply24VDC,250mA
Weight G300 gms. Approx.
Stainless Steel Front Plate110W x 90(H) mm
Display Height Options-0.4″ High Standard,Optional 1″ High Display
Output4-20mA (Optional)

Aerosense Series ADPRHT Clean Room Monitor 

Series ADPRHT Clean Room Monitor Multi-Parameter Display/Transmitter measures Differential Pressure, Humidity, Temperature and optional clock. Series ADPRHT, Multi-parameter display/transmitter measures Differential Pressure, Humidity, Temperature and optional clock. Panel mount/rectangular type cut out for modular wall mounting with stainless steel front plate. Built-in high and low buzzer alarm for process set parameter.

Product Applications:

  • Pharma Cleanrooms, HVAC, Environmental, Pharma machinery, across filters, Hospital isolation room, operation theatres and laboratories.
  • Precision of measurement in HVAC duct pressure application makes this instrument suitable for optimization of energy.
  • Analog output & RS485 communication lead to easy integration with variable frequency drives and SCADA/BMS systems.

Sensor Type:

  • Polymer sensing for Temperature
  • Capacitive polymer sensing for Relative Humidity
  • Piezo Resistive Sensor for Differential Pressure

Range:

  • -30.0 to +50.0 Deg. C typical for Temperature
  • 0.0 to 100.0 % RH typical for Relative humidity
  • 0.0 to +25.0 mm. W.C. / 0 to 250 Pascals (Any other customized range as per user specifications)

Resolution:

  • Fixed 0.1 for both Temperature and Relative humidity 0.1 mm. W.C. or 1 Pascal for Differential Pressure

Accuracy:

  • ±0.5 C for -30 to 50° C for Temperature
  • +/- 1.8% for 10 to 95% RH for Relative humidity
  • +/- 0.5% F.S. for Differential Pressure

Display:

  • 3 Line Red 7 Segment LED Display.
  • 4 Digits for Differential Pressure on Line 1.
  • 4 Digits for % RH. (Humidity) on Line 2.
  • 4 Digits on Temperature (Deg. C) on Line 3.

Differential Pressure Entry:

  • 2 Nos. 4 mm. Hose Nipples at top.

Setting:

  • By 4 keys on the front stainless steel panel.

Buzzer:

  • Integrated buzzer for Alarm in case of process violation of any of the 3 parameters

 

Mounting:

  • Wall mounting / Modular Wall Mounting with Stainless Steel Front Flush Plate for Clean Rooms

Sensors:

  • Integrated Humidity & Temperature Sensor flushed to front plate Built in differential pressure sensor with Brass HoseNipples (Chrome Plated) for Differential Pressure At Rear ( 4 mm x 2 Nos.) Optional External Humidity & Temperature Sensor

Communication:
RS 485 Modbus Protocol (Optional)

 

Enclosure:

  • M.S. Power Coated body with Stainless Steel Front Flush Plate for Modular Wall Mounting/Optional Brick Wall Mounting.

 

Aerosense Clean Room Monitor

 
Minimum Order Quantity1 Number
BrandAerosense
Weight300 gms. Approx
Dimension MmEnclosure: 74(W) x 72(H) x 40(D) mm
Stainless Steel Front Plate110W x 90(H) mm
Output4-20mA (Optional)
Supply Voltage24VDC,250mA

Aerosense Clean Room Monitor

Multi-Parameter Display/Transmitter measures Differential Pressure, Humidity, Temperature and optional clock. Series ADPRHT, Multi-parameter display/transmitter measures Differential Pressure, Humidity, Temperature and optional clock. Panel mount/rectangular type cut out for modular wall mounting with stainless steel front plate. Built-in high and low buzzer alarm for process set parameter.

 

Product Applications:

  • Pharma Cleanrooms, HVAC, Environmental, Pharma machinery, across filters, Hospital isolation room, operation theatres and laboratories.
  • Precision of measurement in HVAC duct pressure application makes this instrument suitable for optimization of energy.
  • Analog output & RS485 communication lead to easy integration with variable frequency drives and SCADA/BMS systems.

Sensor Type:

  • Polymer sensing for Temperature
  • Capacitive polymer sensing for Relative Humidity
  • Piezo Resistive Sensor for Differential Pressure

Range:

  • -30.0 to +50.0 Deg. C typical for Temperature
  • 0.0 to 100.0 % RH typical for Relative humidity
  • 0.0 to +25.0 mm. W.C. / 0 to 250 Pascals (Any other customized range as per user specifications)

Resolution:

  • Fixed 0.1 for both Temperature and Relative humidity 0.1 mm. W.C. or 1 Pascal for Differential Pressure

Accuracy:

  • ±0.5 C for -30 to 50° C for Temperature
  • +/- 1.8% for 10 to 95% RH for Relative humidity
  • +/- 0.5% F.S. for Differential Pressure

Display:

  • 3 Line Red 7 Segment LED Display.
  • 4 Digits for Differential Pressure on Line 1.
  • 4 Digits for % RH. (Humidity) on Line 2.
  • 4 Digits on Temperature (Deg. C) on Line 3.

Techncal Specifications:

  • Display Height Options: -0.4” High Standard, Optional 1” High Display
  • Differential Pressure Entry: 2 Nos. 4 mm. Hose Nipples at top.
  • Setting: By 4 keys on the front stainless steel panel.
  • Buzzer: Integrated buzzer for Alarm in case of process violation of any of the 3 parameters
  • Mounting: Wall mounting / Modular Wall Mounting with Stainless Steel Front Flush Plate for Clean Rooms
  • Sensors: Integrated Humidity & Temperature Sensor flushed to front plate Built in differential pressure sensor with Brass HoseNipples (Chrome Plated) for Differential Pressure At Rear ( 4 mm x 2 Nos.) Optional External Humidity & Temperature Sensor
  • Communication: RS 485 Modbus Protocol (Optional)
  • Enclosure: M.S. Power Coated body with Stainless Steel Front Flush Plate for Modular Wall Mounting/Optional Brick Wall Mounting.

 

 

Series 605 Magnehelic Differential Pressure Indicating Transmitter Wholesaler

Series 605 Magnehelic Differential Pressure Indicating Transmitter

 
Usage/ApplicationMonitor Pressures in Ducts, Rooms,or Total Building Pressures, Filter Monitoring, Local indication of Clean Room Pressures With Process Signal sent to Control Room
BrandDWYER
Model Name/NumberSeries 605
Connection1/8″ female NPT.
Dial Size4″ (101.6 mm) dial face,5″ (127 mm) OD x 2-11/16″ (68.3 mm).
OptionalAir and non-combustible,compatible gases.

The Series 605 Magnehelic Indicating Transmitter provides for both visual monitoring and electronic control of very low differential pressure.The Series 605 is ideal for control applications in building HVAC systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system.The easily read dial gage is complimented by the two-wire, 4 to 20 mA control signal utilizing the time-proven Dwyer Magnehelic gage mechanical design and Series 600 transmitter technology. The two-wire design with terminal strip on the rear simplifies connection in any 4 to 20 mA control loop powered by a 10 to 35 VDC supply.

Product Applications
:
  • Monitor Pressures in Ducts,
  • Rooms,or Total Building Pressures,
  • Filter Monitoring,
  • Local indication of Clean Room Pressures With Process Signal sent to Control Room

Models & Ordering:
  • Model-605-0
  • Range – 0-.50″ w.c.,max. pressure 25 psi (1.7 bar), ±2% electrical accuracy, ±3% mechanical accuracy.
  • Model-605-00N
  • Range – .05-0-0.2″ w.c.,max.pressure 25 psi (1.7 bar),±2% electrical accuracy,±4% mechanical accuracy.
  • Model-605-1
  • Range – 0-1.0″ w.c.,max.pressure 25 psi (1.7 bar), ±2% electrical accuracy,±2% mechanical accuracy.
  • Model-605-10 
  • Range – 0-10″ w.c.,max.pressure 2 psi (13.79 kPa), ±0.5% electrical accuracy,±2% mechanical accuracy.
  • Model-605-11
  • Range – .25-0-.25″ w.c.,max. pressure 25 psi (1.7 bar),±2% electrical accuracy,±3% mechanical accuracy.
  • Model-605-125PA
  • Range – 0-125 Pa,max.pressure 25 psi (1.7 bar), ±2% electrical accuracy, ±3% mechanical accuracy.
  • Model-605-2
  • Range – 0-2.0″ w.c.,max. pressure 2 psi (13.79 kPa), ±0.5% electrical accuracy,±2% mechanical accuracy.
  • Model-605-20
  • Range – 0-20″ w.c.,max.pressure 11 psi (75.8 kPa), ±0.5% electrical accuracy,±2% mechanical accuracy.
  • Model-605-250PA
  • Range – 0-250 Pa,max.pressure 25 psi (1.7 bar), ±2% electrical accuracy,±2% mechanical accuracy.
  • Model-605-3
  • Range – 0-3.0″ w.c.,max.pressure 2 psi (13.79 kPa), ±0.5% electrical accuracy,±2% mechanical accuracy.
  • Model-605-30
  • Range – 0-30″ w.c.,max. pressure 11 psi (75.8 kPa), ±0.5% electrical accuracy,±2% mechanical accuracy.
  • Model-605-50
  • Range – 0-50″ w.c.,max. pressure 11 psi (75.8 kPa), ±0.5% electrical accuracy, ±2% mechanical accuracy.
  • Model-605-500PA
  • Range – 0-500 Pa,max. pressure 2 psi (13.79 kPa),±0.5% electrical accuracy,±2% mechanical accuracy.
  • Model-605-6 
  • Range – 0-6.0″ w.c.,max. pressure 2 psi (13.79 kPa),±0.5% electrical accuracy, ±2% mechanical accuracy.
  • Model-605-60PA 
  • Range – 0-60 Pa, max. pressure 25 psi (1.7 bar), ±2% electrical accuracy, ±4% mechanical accuracy.
 

Dwyer 605-0 Magnehelic Differential Pressure Indicating Transmitter 0-.50 Inch

 
Usage/ApplicationMonitor Pressures in Ducts, Rooms,or Total Building Pressures, Filter Monitoring, Local indication of Clean Room Pressures With Process Signal sent to Control Room
BrandDWYER
Model Name/NumberDwyer 605-0
Power Supply10 to 35 VDC (2-wire)
Range0-.50 Inch
ApplicationsMonitor Pressures in Ducts,Rooms,or Total Building Pressures,Filter Monitoring,Local indication o
Dial Size4″ (101.6 mm) dial face,5″ (127 mm) OD x 2-11/16″ (68.3 mm)
Size4 INCH AND 101.6 mm
Weight1 lb,12.6 oz (811 g)


Dwyer 605-0 Magnehelic Differential Pressure Indicating Transmitter 0-.50 Inch

  • Model: 605-0

Provides for both visual monitoring and electronic control of very low differential pressure. Ideal for control applications in building HVAC/R systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system.

Dwyer 605-0 MAGNEHELIC, INDICATING TRANSMITTER, 0-.50

  • Easy to read dial gauge is complimented by the two-wire, 4-20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gauge mechanical design and Series 600 transmitter technology.
  • The two-wire design with terminal strip on the rear simplifies connection in any 4-20 mA control loop powered by a 10-35 VDC supply.

Gauge Specifications:

  • Service: Air and non-combustible, compatible gases.
  • Accuracy: +/-3%.
  • Stability: ±1% F.S./yr.
  • Pressure Limits: 25 psi (1.7 bar).
  • Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
  • Process Connections: 1/8″ female NPT.
  • Size: 4″ (101.6 mm) dial face, 5″ (127 mm) O.D.x 2-11/16″ (68.3 mm).
  • Weight: 1 lb, 12.6 oz (811 g).
  • Agency Approvals: CE.

Transmitter Specifications:

  • Accuracy: +/-2% (includes linearity, hysteresis, repeatability).
  • Temperature Limits: 20 to 120°F(-6.67 to 48.9°C).
  • Compensated Temperature Range: 32 to 120°F (0 to 48.9°C).
  • Thermal Effect: ±0.025% F.S./°F (0.045% F.S./°C).
  • Power Requirements: 10-35 VDC (2-wire).
  • Output Signal: 4 to 20 mA.
  • Zero and Span Adjustments: Protected potentiometers.
  • Loop Resistance: DC; 0-1250 ohms maximum.
  • Current Consumption: DC; 38 mA maximum.
  • Electrical Connections: Screw terminal block.
  • Mounting Orientation: Diaphragm in vertical position.


Dwyer 605-0 Specifications

Gauge
ServiceAir and non-combustible, compatible gases
Stability±1% FS/yr
Temperature Limits20 to 120°F (-6.67 to 48.9°C)
Process Connections???” female NPT
Size4″ (101.6 mm) dial face, 5″ (127 mm) OD x 2-11/16″ (68.3 mm)
Weight1 lb, 12.6 oz (811 g)
Agency ApprovalsCE
Transmitter
Temperature Limits20 to 120°F (-6.67 to 48.9°C)
Compensated Temperature Range32 to 120°F (0 to 48.9°C)
Thermal Effect±0.025% FS/°F (0.045% FS/°C)
Power Requirements10 to 35 VDC (2-wire)
Output Signal4 to 20 mA
Zero and Span AdjustmentsProtected potentiometers
Loop ResistanceDC: 0 to 1250 Ω maximum
Current ConsumptionDC: 38 mA maximum
Electrical ConnectionsScrew terminal block
Mounting OrientationDiaphragm in vertical position

DPG DIGITAL PRESSURE GAUGE-Winters Instruments India

Winter LCD Digital Pressure Gauge

 
Minimum Order Quantity12 Piece
BrandWinter
Measuring RangeAs Per Your Requirements
Model Name/NumberDPG
Usage/ApplicationIndustrial
MaterialABS
ConnectionNew
Display TypeLCD
TypeLCD
ColorBlack
Scale Range2.5 INCH
Accuracy0.5%
Diameter63 MM
Dial Size63 MM
Size63 MM
Country of OriginMade in India

Winter LCD Digital Pressure Gauge

Case Size: 2.5” (63 MM)

Case Material: ABS Rubber Boot Silicone Rubber

LCD Display: 2” x 3/4” (48 MM x 16 MM)

Connection: 1/4” NPT 304SS Sensor 316L Welded,

Piezo Operating Life 1 Million Cycles

Power Supply: 2 x AAA Battery (1.5V) Battery Life 2 Yrs (Auto Shut-Off Mode)

Power Mode: Auto Or Manual Shut-Off

Display Digits:  4 Digits to 5,000 PSI 5 Digits For 10,000 PSI And 15,000 PSI

Pressure Unit Selection: psi, mH2 O, mmHg, mbar, kPa ranges ≤ 100 psi,psi, bar, kgf/cm2 , MPa, atm Ranges ≥ 160 psi

 

Winter Digital Pressure Gauge 0 To 60 Bar

 
Minimum Order Quantity12 Number
BrandWinters Canada
Measuring Range0-60 bar
Model Name/NumberDPG231R11
Usage/ApplicationIndustrial
MaterialSteel
ConnectionNew
Display Typeyas
TypeDPG231R11
ColorBlack
I Deal InNew Only
Battery IncludedYes
Country of OriginMade in India

Winter Digital Pressure Gauge 0 To 60 Bar

Product Description:

  • Winters Dpg Digital Pressure Gauge

Applications:

  • Ideal for commercial and industrial applications in both test measurement and general purpose installations

Description & Features:

  • Simple 2 button operation
  • Reset to zero feature
  • Backlight turns on when on/off button is pressed
  • Option for display to remain continuously on 
  • Continuous Peak pressure indication option
  • 316L welded diaphragm seal
  • Rubber boot is standard
  • ASME B40.100 compliant
  • RoHS compliant
  • ±1% accuracy (±0.5% optional for gauges up to 10,000 psi)
  • 1 year warranty

Aerosense Differential Pressure Controller Wholesaler

DPI2500-2R-D Aerosense Differential Pressure Controller

 
Usage/ApplicationFan,Blower And Filter Monitoring
BrandAerosense
MaterialABS
Model Name/NumberDPI2500-2R-D
Pressure Range100 / 250 / 1000 / 2500 PA AND +-100 Pa / +-250 / +-300 / +-500 PA
Size89 x 86.5 x 37.1 mm

Aerosense Differential Pressure Controller Aerosense Differential Pressure Controller with field selectable measuring range for building automation in HVAC/R industry.

Features:
  • Unit selectable via menu i.e. PA, kPA, MM WC, IN WC, MBAR
  • Combines up to two relay outputs
  • Optional Auto-Zero feature which electronically adjusts the transmitter zero at predetermined time intervals (every 10 minutes)
  • The AZ-calibration eliminates all output signal drift due to thermal, electronic or mechanical effects

Applications:
  • Fan, Blower and Filter Monitoring
  • Pressure Monitoring in Clean Rooms
  • Boiler Pressure Monitoring and Alarm
 

DPI2500-2R-D Aerosense Differential Pressure Controller

 
BrandAerosense
Electrical ConnectionScrew Terminals
Model Name/NumberDPI2500-2R-D
Size46.0 W x 14.5 H mm
Weight150 g
Warranty Period6 month
Accuracy+-0.5 % F.S.

DPI2500-2R-D Aerosense Differential Pressure Controller Aerosense Differential Pressure Controller with field selectable measuring range for building automation in HVAC/R industry.

Features:
  • Unit selectable via menu i.e. PA, kPA, MM WC, IN WC, MBAR
  • Combines up to two relay outputs
  • Optional Auto-Zero feature which electronically adjusts the transmitter zero at predetermined time intervals (every 10 minutes)
  • The AZ-calibration eliminates all output signal drift due to thermal, electronic or mechanical effects

Applications:
  • Fan, Blower and Filter Monitoring
  • Pressure Monitoring in Clean Rooms
  • Boiler Pressure Monitoring and Alarm
 

DPIC500-2R-D Aerosense Differential Pressure Controller

 
BrandAerosense
Case Size89 x 86.5 x 37.1 mm
Control TypeHigh Limit
MaterialABS
Model Name/NumberDPIC500-2R-D
Pressure Range+-100 Pa / +-250 / +-300 / +-500 PA
Warranty6 month
Accuracy+-0.5 % F.S.
Weight150 g
ApplicationsFan,Blower And Filter Monitoring

DPIC500-2R-D Aerosense Differential Pressure Controller Aerosense Differential Pressure Controller with field selectable measuring range for building automation in HVAC/R industry.

Features:
  • Unit selectable via menu i.e. PA, kPA, MM WC, IN WC, MBAR
  • Combines up to two relay outputs
  • Optional Auto-Zero feature which electronically adjusts the transmitter zero at predetermined time intervals (every 10 minutes)
  • The AZ-calibration eliminates all output signal drift due to thermal, electronic or mechanical effects

Applications:
  • Fan, Blower and Filter Monitoring
  • Pressure Monitoring in Clean Rooms
  • Boiler Pressure Monitoring and Alarm
 

Aerosense Carbon Dioxide Transmitter Wholesalers

CDT-100 Aerosense Carbon Dioxide Transmitter

 
Minimum Order Quantity1 Piece
Model NumberCDT-100
Usage/ApplicationDemand Control Ventilation In Schools,Office Buildings,Hospitals And Other Indoor Environments
BrandAerosense
Measurement Range0 to 2000/ 3000/ 5000/ 10000 ppm
Accuracy+-30ppm +-3%
Operating Humidity Range0 to 95% RH
Operating Temperature-10 to 60 deg C
Power24 VDC,AC
Size123x70x43 mm
Storage Temperature-30 to 70 deg C
Storage Temperature for Cold Storage-40 to 70 deg C
Response Time150 seconds
Response Time For Cold Storage70 Seconds
Sampling Interval3 Sec

CDT-100 Aerosense Carbon Dioxide Transmitter Series CDT-100, Carbon Dioxide Transmitter accurately monitors the CO2 concentration in indoor environments to help achieve energy savings. For increased sensor accuracy, a single beam dual wavelength non-dispersive infrared (NDIR) sensor is used to automatically correct the measurements. Measurement range upto 10000 ppm selectable by jumper. It gives analog and RS-485 MODBUS output and supports various functions like recalibration function.

Product Applications:

  • Demand Control Ventilation in schools, office buildings, hospitals and other indoor environments.
  • CO2 Sensor: NDIR (Non-Dispersive Infrared) technology
  • Analog Voltage/Current Output: (3-wired) 0/4-20Ma or 0/2-10V- settable by switch
  • RS-485 MODBUS output: (4-wired) Modicon MODBUS RTU mode, which follow Modicon Modbus protocol-settable address ID switch
  • Re-Calibration function: 10 minutes’ manual recalibration(MCDL) Or weekly auto-calibration (ACDL) are supported and settable by Switch CO2 ppm measurement range -settable by switch

Model No. CDT-100Carbon Dioxide TransmitterCDT-100-LCDCarbon Dioxide Transmitter with displayCDT-100-CSCarbon Dioxide Transmitter for cold storageCDT-100-CS-LCDCarbon Dioxide Transmitter for cold storage with display CDT-100-M Carbon Dioxide Transmitter with MODBUS Communication CDT-100-M-LCD Carbon Dioxide Transmitter with MODBUS Communication & display
 

CDT-100-RLY Aerosense Carbon Dioxide Transmitter

 
Minimum Order Quantity1 Piece
UsageDemand Control Ventilation In Schools,Office Buildings,Hospitals And Other Indoor Environments
ModelSeries CDT-100-RLY
Size123mmx70mmx43mm
Response Time150 seconds
BrandAerosense
Operating Temperature10 to 60 deg C
Storage temperature-30 to 70 deg C

 

CDT-100-RLY Aerosense Carbon Dioxide Transmitter, Carbon Dioxide Transmitter accurately monitors the CO2 concentration in indoor environments to help achieve energy savings. For increased sensor accuracy, a single beam dual wavelength non-dispersive infrared (NDIR) sensor is used to automatically correct the measurements. Measurement range 2000 ppm (5000/10000 ppm) selectable by jumper. It gives analog and Relay output and supports various functions like recalibration function.

Product Applications:

  • Demand Control Ventilation in schools, office buildings, hospitals and other indoor environments.
  • CO2 Sensor: NDIR (Non-Dispersive Infrared) technology
  • Analog Voltage/Current Output: (6-wired) 0/4-20Ma or 0/2-10V- settable by switch
  • Models available with SPST (Single Pole, Single Throw, normally open) relay output.
  • Re-Calibration function: 10 minutes’ manual recalibration is executable with TRB-100 tool

CDT-300 Aerosense Carbon Dioxide Transmitter

 
Minimum Order Quantity1 Piece
Model NumberSeries CDT-300
Usage/ApplicationDemand Control Ventilation In Schools,Office Buildings,Hospitals And Other Indoor Environments
BrandAerosense
Size123mmx70mmx43mm
Response Time150 Seconds
Operating Temperature-10 to 60 deg C
Operating Humidity range0 to 95% RH
Storage temperature-30 to 70 deg C
Power24 V Dc


CDT-300 Aerosense Carbon Dioxide Transmitter Series CDT-300, Carbon Dioxide Transmitter accurately monitors the CO2 concentration in indoor environments to help achieve energy savings. For increased sensor accuracy, a single beam dual wavelength non-dispersive infrared (NDIR) sensor is used to automatically correct the measurements. Measurement range upto 70000 ppm selectable by jumper. It gives analog and RS-485 MODBUS output and supports various functions like recalibration function.

Product Applications:

  • Demand Control Ventilation in schools, office buildings, hospitals and other indoor environments.
  • CO2 Sensor: NDIR (Non-Dispersive Infrared) technology
  • Analog Voltage/Current Output: (3-wired) 0/4-20Ma or 0/2-10V- settable by switch
  • Re-Calibration function: 10 minutes’ manual recalibration(MCDL) Or weekly auto-calibration (ACDL) are supported and settable by Switch CO2 ppm measurement range -settable by switch

 

Model No.Speci???cations
CDT-300Carbon Dioxide Transmitter
CDT-300-LCDCarbon Dioxide Transmitter with display